      1. 安全阀压力试验机的试验方法

        2014-04-07 0

        1、耐压(液压强度)试验

        应当符合以下要求:

        (1)安全阀耐压(液压强度)试验在涂(喷)漆之前进行;

        (2)封闭安全阀阀座的密封面,对安全阀进口侧体腔进行耐压(液压强度)试验,最小试验压力为安全阀公称压力(压力级)的1.5倍;

        (3)对于向大气排放的安全阀或者仅在排放时产生背压力的安全阀,不要求在阀体出口排放侧进行耐压(液压强度)试验;

        (4)当安全阀承受附加背压或者安装于封闭的排放系统时,则需要在阀体出口排放出口排放侧进行耐压(液压强度)试验;

        (5)耐压(液压强度)试验持续时间按GB/T12241-2005《安全阀 一般要求》的规定,并且对阀体(盖)各表面和连接处进行宏观检查。如果试验过程中没有出现变形、裂缝与泄漏等现象。则表明耐压(液压强度)试验合格。

        2、气密封试验

        对于封闭式安全阀、整体组装后,应当进行气密封试验。气密封试验应当符合以下要求:

        (1)试验只在阀体出口排放侧部位进行,压力为最大背压力,并且不小于0.2MPa;

        (2)试验持续时间3min,不允许泄漏;

        (3)试验时要注意安全,达到试验压力一定时间后再进行气密性检查。